Analysis of losses in fan coil units by using the entropy-statistical method
- Authors: Osipenko V.V.1, Lavrov N.A.2
-
Affiliations:
- VEZA
- Bauman Moscow State Technical University
- Issue: Vol 111, No 1 (2022)
- Pages: 5-12
- Section: Original Study Articles
- URL: https://freezetech.ru/0023-124X/article/view/100464
- DOI: https://doi.org/10.17816/RF100464
- ID: 100464
Cite item
Full Text
Abstract
BACKGROUND: Systems with chillers and fan coil units are widely used in air conditioning. Therefore, entropy-statistical analysis of energy losses in a duct-type two-pipe fan coil unit with controlled air flow is relevant.
AIM: This work aimed to review a method for determining losses by using the entropy-statistical method and to calculate losses due to non-ideal heat transfer and hydraulic losses in fan coil units.
MATERIALS AND METHODS: Losses were determined using the entropy-statistical method.
RESULTS: A comparative analysis of the results was performed. Diagrams of the distribution of loss components and recommendations for their reduction are presented.
Full Text
ВВЕДЕНИЕ
Экономия энергии – одна из основных задач современной науки и техники. Поскольку низкотемпературные установки потребляют 13–18% всей вырабатываемой в мире электроэнергии, снижение их энергопотребления за счет уменьшения имеющихся в них потерь – задача актуальная. Для анализа потерь в низкотемпературных установках наиболее эффективным методом признан метод энтропийного анализа [1], с помощью которого можно выполнить анализ потерь в отдельных частях холодильной установки [2–4], локализовать места наибольших потерь и выработать технические решения для их уменьшения [5–8].
Системы с чиллерами и фанкойлами [9] широко применяются в кондиционировании воздуха, поэтому анализ потерь в них имеет существенное значения для реализации мер по сокращению энергопотребления.
Рассмотрим фанкойл, в котором происходит охлаждение воздуха, движимого вентилятором. В качестве прототипа принимаем канальный двухтрубный фанкойл ВЕНДО-КС-10/2-Н с регулируемым расходом воздуха от 850 до 1700 м3/ч, производительностью на охлаждение 9,0 кВт, изображенный на рис. 1. Охлаждающая жидкость – вода.
Рис. 1. Канальный двухтрубный двухтрубный фанкойл ВЕНДО-КС-10/2-Н. / Fig. 1. Duct-type two-pipe fan coil unit VENDO-KS-10/2-N.
Затрачиваемая на охлаждение воздуха работа L может быть разделена на две составляющие:
- минимальная (теоретическая) работа , при которой процессы возможны только теоретически;
- работа на компенсацию потерь вследствие необратимости :
.
С точки зрения энтропийно-статистического метода, потери энергии пропорциональны производству энтропии.
Согласно теореме Гюи – Стодолы [1], потери энергии в системе за счет неравновесности протекающих в ней процессов пропорциональны производству энтропии в системе :
где Тос — температура окружающей среды. Определение производства энтропии в отдельных частях установки позволяет найти наиболее энергозатратный элемент рассматриваемой системы и попытаться уменьшить необратимость в найденном элементе.
К потерям следует отнести следующие.
- Потери из-за несовершенства теплообмена между охлаждающей жидкостью и воздухом в фанкойле.
- Гидравлические потери при прохождении воздуха через фанкойл, которые выражаются через мощность вентилятора и кинетическую энергию выходящего воздуха.
- Гидравлические потери при прохождении охлаждающей жидкости через теплообменник фанкойла, которые приводят к увеличению требуемой мощности жидкостного насоса.
Расчет потерь
- Потери вследствие несовершенства теплообмена между охлаждающей жидкостью и воздухом в фанкойле.
Потери вследствие неидеальности теплообмена в фанкойле можно рассчитать через производство энтропии как суммарное изменение энтропии воздушного потока и охлаждающей жидкости :
, (1)
, (2)
, (3)
где и – теплоемкости воздуха и жидкости в фанкойле соответственно; Gв и Gж – расходы воздуха и жидкости в фанкойле соответственно; Тв,вх и Тв,вых, Тж,вх и Тж,вых – термодинамические температуры воздуха и жидкости на входе и выходе из фанкойла.
- Гидравлические потери при прохождении воздуха через фанкойл выражаются через мощность вентилятора и кинетическую энергию выходящего воздуха:
, (4)
где — мощность, потребляемая вентилятором, — термодинамическая температура окружающей среды. Массовый расход воздуха, проходящего через фанкойл Gв, рассчитывается по формуле
, (5)
где на выходе из фанкойла – плотность воздуха при температуре и давлении, — площадь проходного сечения, — скорость воздуха.
Мощность, потребляемую вентилятором, можно определить как произведение действующего напряжения в сети U, от которого запитывается вентилятор (обычно 220 В/230 В), на действующее значение силы тока I в цепи вентилятора:
Nвент=UI. (6)
- Гидравлические потери при прохождении охлаждающей жидкости через теплообменник фанкойла, приводящие к увеличению потребляемой мощности жидкостного насоса:
, (7)
где – КПД насоса, — объемный расход жидкости, выходящей из насоса, м3/с, — потеря напора жидкости при прохождении жидкостного теплообменника в фанкойле, Па, — температура окружающей среды, К.
Для измерения требуемых параметров использовалось следующее оборудование.
- Термометры, измеряющие температуру воздуха на входе Тв,вх и выходе Тв,вых из фанкойла.
- Термометры, измеряющие температуру охлаждающей жидкости на входе Тж,вх и выходе Тж,вых из фанкойла.
- Манометры для измерения давления охлаждающей жидкости на входе рж,вх и выходе рж,вых из фанкойла.
- Расходомер, измеряющий расход охлаждающей жидкости, протекающей через фанкойл. При пересчете использован объемный расход Qж.
- Анемометры, измеряющие скорость воздуха на входе и выходе из фанкойла.
- Амперметр для измерения силы тока в цепи вентилятора I.
- Вольтметр для измерения напряжения в цепи вентилятора U.
Измерения проводились при следующих параметрах:
- давление жидкости на входе рж,вх=150 Па;
- температура жидкости на входе в фанкойла Тж,вх=7 °С;
- температура жидкости на выходе из фанкойла Тж,вых=12 °С;
- напряжение U=220 В;
- проходное сечение вход 0,24 м2;
- проходное сечение выход 0,18 м2.
Измерения проводились в фанкойле с расходом воздуха от 850 до 1700 м3/ч каждые два часа в течение суток (табл. 1).
Таблица 1. Результаты измерений / Table 1. Measurement results
№ | Время замера | Температура воздуха на входе, Тв,вх | Относительная влажность воздуха на входе, ϕнарвх | Температура воздуха на выходе, Тв,вых | Относительная влажность, ϕнар. вых | Давление жидкости на выходе, рж,вых | Объемный расход Qж | Расход воздуха | Скорость воздуха на входе | Скорость воздуха на выходе | Сила тока, I |
чч:мм | °С | % | °С | % | Па | л/с | м3/ч | м/с | м/с | А | |
1 | 06:00 | +24 | 63 | +12,8 | 95 | 126 | 0,38 | 1275 | 1,48 | 1,97 | 0,52 |
2 | 08:00 | +25 | 57 | +13,7 | 95 | 126 | 0,38 | 1275 | 1,48 | 1,97 | 0,52 |
3 | 10:00 | +26 | 52 | +13,7 | 95 | 126 | 0,38 | 1275 | 1,48 | 1,97 | 0,52 |
4 | 12:00 | +27 | 47 | +13,7 | 95 | 118 | 0,43 | 1700 | 1,97 | 2,62 | 0,78 |
5 | 14:00 | +27 | 47 | +13,7 | 95 | 118 | 0,43 | 1700 | 1,97 | 2,62 | 0,78 |
6 | 16:00 | +27 | 47 | +13,7 | 95 | 118 | 0,43 | 1700 | 1,97 | 2,62 | 0,78 |
7 | 18:00 | +26 | 52 | +13,7 | 95 | 118 | 0,43 | 1700 | 1,97 | 2,62 | 0,78 |
8 | 20:00 | +25 | 57 | +12,8 | 96 | 126 | 0,43 | 1275 | 1,48 | 1,97 | 0,52 |
9 | 22:00 | +23 | 69 | +12,5 | 96 | 125 | 0,43 | 1275 | 1,48 | 1,97 | 0,52 |
10 | 00:00 | +20 | 91 | +13,0 | 97 | 125 | 0,43 | 1275 | 1,48 | 1,97 | 0,52 |
На основании результатов эксперимента проведем необходимые расчеты.
1. По температуре и относительной влажности воздуха на входе и выходе из вентилятора определяем плотность воздуха ρв,вх и ρв,вых при атмосферном давлении 101 325 Па (табл. 2), а также по средним параметрам (Тв,вх = 19 ˚С и ϕнарвх = 76,8%) теплоемкость воздуха рассчитываем по формуле:
, (8)
где 1,005 и 1,8 кДж/кг·К – теплоемкости сухого воздуха и водяного пара соответственно, d = 10,54 г/кг – влагосодержание воздуха при средних параметрах.
кДж/кг·К. (9)
Таблица 2. Результаты измерений параметров воздуха в фанкойле / Table 2. Results of measurements of air parameters in a fan coil unit
№ замера | Время замера | Плотность воздуха ρв, вх | Плотность воздуха ρв, вых | Расход воздуха Gв,вх | Расход воздуха Gв,вых | Расход воздуха средний Gв, | Потеря давления Δр | Мощность вентилятора, Nвент |
чч:мм | кг/м3 | кг/м3 | кг/с | кг/с | кг/с | Па | Вт | |
1 | 06:00 | 1,18 | 1,23 | 0,419 | 0,436 | 0,428 | 24 | 114,4 |
2 | 08:00 | 1,18 | 1,22 | 0,419 | 0,433 | 0,426 | 24 | 114,4 |
3 | 10:00 | 1,17 | 1,22 | 0,416 | 0,433 | 0,425 | 24 | 114,4 |
4 | 12:00 | 1,17 | 1,22 | 0,553 | 0,575 | 0,564 | 32 | 171,6 |
5 | 14:00 | 1,17 | 1,22 | 0,553 | 0,575 | 0,564 | 32 | 171,6 |
6 | 16:00 | 1,17 | 1,22 | 0,553 | 0,575 | 0,564 | 32 | 171,6 |
7 | 18:00 | 1,17 | 1,22 | 0,553 | 0,575 | 0,564 | 32 | 171,6 |
8 | 20:00 | 1,18 | 1,23 | 0,419 | 0,436 | 0,428 | 24 | 114,4 |
9 | 22:00 | 1,18 | 1,23 | 0,419 | 0,436 | 0,428 | 25 | 114,4 |
10 | 00:00 | 1,19 | 1,23 | 0,423 | 0,436 | 0,430 | 25 | 114,4 |
2. По формуле (5) определяем массовый расход воздуха на входе и выходе из фанкойла (результаты приведены в табл. 2). В случае несовпадения этих величин, для дальнейших вычислений берем среднее значение.
3. По разности давлений жидкости на входе и выходе определяем потерю давления (табл. 2) как:
. (10)
По средним параметрам воды (Тж,ср = 9,5 °С, рж,ср = 136,3 Па) определяем величину удельной объемной теплоемкости при этих условиях:
Сж = 4190,8 кДж/(м3.К). (11)
4. По формулам (1)—(3) рассчитываем производство энтропии вследствие неидеальности теплообмена в фанкойле (в табл. 3). На рис. 2 представлена гистограмма потерь энергии от неидеальности теплообмена в зависимости от номера измерения.
Таблица 3. Результаты измерений температур в фанкойле / Table 3. Results of temperature measurements in the fan coil unit
Номер замера | Время замера | Температура окружающей среды Тос | Температура окружающей среды Тос |
№ | чч:мм | °С | К |
1 | 06:00 | +18,4 | 291,5 |
2 | 08:00 | +19,4 | 292,5 |
3 | 10:00 | +19,9 | 293,0 |
4 | 12:00 | +20,4 | 293,5 |
5 | 14:00 | +20,4 | 293,5 |
6 | 16:00 | +20,4 | 293,5 |
7 | 18:00 | +19,9 | 293,0 |
8 | 20:00 | +18,9 | 292,0 |
9 | 22:00 | +17,8 | 290,9 |
10 | 00:00 | +16,5 | 289,6 |
Рис. 2. Потери энергии вследствие неидеальности теплообмена. / Fig. 2. Energy losses due to non-ideal heat transfer.
5. По формуле (6) определяем мощность, потребляемую вентилятором (результаты представлены в табл. 2), а по выражению (4) – производство энтропии в вентиляторе вследствие гидравлических потерь (табл. 4), температуру окружающей среды принимаем как среднюю входных и выходных температур воздуха (табл. 3).
Таблица 4. Производство энтропии в фанкойле / Table 4. Entropy production in a fan coil unit
Номер замера | Время замера | ΔSто | ΔSвент | ΔSнасос |
№ | чч:мм | Вт/К | Вт/К | Вт/К |
1 | 06:00 | 11,34 | 0,390 | 3,630E-05 |
2 | 08:00 | 11,32 | 0,388 | 3,617E-05 |
3 | 10:00 | 9,90 | 0,388 | 3,611E-05 |
4 | 12:00 | 5,70 | 0,578 | 5,439E-05 |
5 | 14:00 | 5,70 | 0,578 | 5,439E-05 |
6 | 16:00 | 5,70 | 0,578 | 5,439E-05 |
7 | 18:00 | 7,63 | 0,579 | 5,448E-05 |
8 | 20:00 | 9,86 | 0,389 | 3,623E-05 |
9 | 22:00 | 12,35 | 0,390 | 3,789E-05 |
10 | 00:00 | 17,53 | 0,392 | 3,806E-05 |
На рис. 3 приведена величина потерь в вентиляторе для каждого измерения.
Рис. 3. Величина потерь энергии в вентиляторе. / Fig. 3. Energy loss in the fan.
- По формуле (7) рассчитываем производство энтропии вследствие гидравлических сопротивлений жидкости при прохождении жидкостного теплообменника в фанкойле (табл. 2) и строим гистограмму в зависимости от номера измерения (рис. 4). КПД насоса задаем, исходя из принятого прототипа гидромодуля АкваВЕНС 2.0 КН-Р4-1Н и насоса в этом гидромодуле: Ebara DWC-V 500/2.2 (КПД равен 0,862 при 100% загрузке).
Рис. 4. Гидравлические потери от прохождения жидкости через теплообменник. / Fig. 4. Hydraulic losses from the passage of liquid through the heat exchanger.
7. Результаты расчета производства энтропии в фанкойле представлены в табл. 4.
Таким образом, создана методика определения потерь в фанкойлах с помощью энтропийного метода, которая позволила определить составляющие потерь в фанкойле и их вклад в суммарные потери.
ВЫВОДЫ
- Анализ полученных результатов показывает, что потери, связанные с неидеальностью теплообмена в фанкойле в 10 раз выше, чем гидравлические потери при прохождении воздуха и охлаждающей жидкости через фанкойл.
- Основным направлением для снижения потерь должно быть повышение эффективности процесса теплообмена, которое может быть достигнуто за счет увеличения площади теплообмена, и как следствие, снижения перепада температур.
- Гидравлические потери от движения воздуха и жидкости составляют не более 10٪ от общего энергопотребления, и хотя вносят свой вклад в потребляемые мощности вентилятора в фанкойле и насоса в гидромодуле, несколько увеличивая их, но в то же время незначительно влияют на общее энергопотребление.
ДОПОЛНИТЕЛЬНО
Финансирование. Статья не имеет спонсорской поддержки.
Конфликт интересов. Авторы заявляют об отсутствии конфликта интересов, связанного с подготовкой и публикацией статьи.
Вклад авторов. Все авторы внесли существенный вклад в разработку концепции, проведение исследования и подготовку статьи, прочли и одобрили финальную версию перед публикацией.
ADDITIONAL INFORMATION
Competing interests. The author declares no any transparent and potential conflict of interests in relation to this article publication.
Funding source. Article is not sponsored.
Contribution of authors. All authors made a significant contribution to the development of the concept, research and preparation of the article, read and approved the final version before publication.
About the authors
Valentina V. Osipenko
VEZA
Email: region@veza.ru
Engineer
Russian Federation, Moscow RegionNikolai A. Lavrov
Bauman Moscow State Technical University
Author for correspondence.
Email: 79035596471@yandex.ru
SPIN-code: 9187-7444
Dr. Sci. (Tech.), Professor
Russian Federation, 5, 2-nd Baumanskaya, Moscow, 105005References
- Arharov AM. Osnovy kriologii. Jentropijno-statisticheskij analiz nizkotemperaturnyh sistem. Moscow: Izdatel’stvo MGTU im. N.Je. Baumana, 2014, 507 p. (in Russ.).
- Shishov VV, Talyzin MS. Prakticheskoe primenenie jentropijno-statisticheskogo metoda analiza holodil’nyh ciklov. Refrigeration Technology. 2015;104(3):25–30. (in Russ.). doi: 10.17816/RF98878
- Arharov AM, Shishov VV, Talyzin MS. Jentropijno-statisticheskij analiz nizkotemperaturnyh holodil’nyh ciklov i vybor na ego osnove optimal’noj sistemy holodosnabzhenija magazina. Refrigeration Technology. 2016;105(3):30–34. (in Russ.). doi: 10.17816/RF99047
- Zdobnov MI, Lavrov NA, Shishov VV. Analiz poter’ v teploobmennike teploutilizatore s pomoshh’ju jentropijno-statisticheskogo metoda. Refrigeration Technology. 2019;108(2): 37–40. (in Russ.). doi: 10.17816/RF99501
- Zdobnov MI, Lavrov NA, Shishov VV, Karakulov SI. Analiz poter’ v isparitel’no kondensatornom konture central’nogo kondicionera s pomoshh’ju jentropijno-statisticheskogo metoda. Refrigeration Technology. 2019;108(8):28–33. (in Russ.). doi: 10.17816/RF104152
- Zdobnov MI, Lavrov NA. Analiz poter’ v ventiljacionnyh ustanovkah s pomoshh’ju jentropijno-statisticheskogo metoda. Refrigeration Technology. 2018;107(8):36–41. (in Russ.). doi: 10.17816/RF99432
- Tishhenko IV, Abalakin SA, Merkulov VI, et al. Jentropijno-statisticheskij analiz sistemy kondicionirovanija vozduha passazhirskogo samoleta. Holodil’naja i kriogennaja tehnika, sistemy kondicionirovanija i zhizneobespechenija: materialy Tret’ej mezhdunarodnoj nauchnoj konferencii. 2020, p. 318–326. (in Russ.).
- Arharov AM, Arharov IA, Sychjov VV, et al. O rezul’tatah jentropijnogo i jeksergeticheskogo analiza processa smeshenija chastej ideal’nogo gaza raznoj temperatury // Refrigeration Technology. 2014;103(7):35–39. (in Russ.). doi: 10.17816/RF98779
- Belova EM. Sistemy kondicionirovanija s chillerami i fjenkojlami. Moscow: Izd-vo Evroklimat, 2003, 400 p. (in Russ.).